Caracteristici
Ambient temperature, maximum:
60
Ambient temperature, minimum:
-25
AS-i Current consumption, maximum:
100
AS-i Device protection:
Internal short-circuit proof
AS-i Input, Channel 1:
Data bits DI 0 / DI 1 = dynamic code transmission
AS-i Input, Channel 2:
Data bits DI 2 / DI 3 = dynamic code transmission
AS-i Operating voltage AS-i maximum:
31.6
AS-i Operating voltage, minimum:
18
AS-i Outputs, DO 0 … DO 3:
No Function
AS-i Parameter bits, P0:
Actuator in
AS-i Parameter bits, P1:
Enabling inhibit (tamper protection time) active (FID))
AS-i Parameter bits, P2:
No function
AS-i Parameter bits, P3:
Internal device error (FID)
AS-i Specification:
Safety-Slave
Basic quantity unit:
Piece
Certificates:
cULus; TÜV; EAC; FCC; ASi-SaW
Coding level according to ISO 14119:
High
Control category to EN13849:
4
Degree of pollution to VDE 0100:
3
Duration of risk, maximum:
200
EAN (European Article Number):
4030661507606
eCl@ss number, Version 9.0:
27-27-24-03
Enclosure material:
Thermoplastic hotmelt
Ensured switch distance "OFF" Sar, lateral:
15
Ensured switching distance "OFF", front:
18
Ensured switching distance "ON", front:
10
Ensured switching distance "ON", side:
6
general information:
Individual coding
Hysteresis (Switch distance), maximum:
2
Included in delivery:
Actuators must be ordered separately.
Integral System Diagnostics, status :
Yes
Note (AS-i Parameter bits):
Set the parameter outputs to "1111" (0xF) ; FID: periphery error
Note (AS-i Input module address):
Preset to address 0, can be changed through AS-interface bus master or hand-held programming device
Note (AS-i Operating voltage):
Protection against polarity reversal
Note (LED switching conditions display):
(1) green/red LED (AS-i Duo LED):Supply voltage / communication error / slave address = 0 / periphery error detected / Tamper protection time active; (2) yellow LED: device condition (enabling status) / hysteresis signal / device error
Number of actuating directions:
2
Overvoltage category:
III
Overvoltage category to VDE 0100:
3
Performance level, up to:
e
PFH-value:
0.000000000393
Protection class (Operating resource):
3
Rated impulse withstand voltage:
0.8
Rated insulation voltage:
32 VDC
Reaction time, maximum:
100
Recommendation (actuator):
RST260-1
Resistance to vibrations to EN 60068-2-6:
10 … 55 Hz, amplitude 1 mm
Restistance to shock:
30 g / 11 ms
Safety Integrity Level (SIL), applicable for:
3
Storage and transport temperature, maximum:
85
Storage and transport temperature, minimum:
-25
Switch distance:
12 mm; 9 mm (in case of approach from side)
Switching frequency, maximum:
1
Terminal Connector:
Connecting cable with M12 connector, straight, 4-pole
Time to readiness, maximum:
2000
Safety-relevant key characteristics
Housing
ambient conditions
protection class:
IP 67 to IEC/EN 60529; IP 65 to IEC/EN 60529