Ambient temperature, maximum:
60
Ambient temperature, minimum:
-25
AS-i Device protection:
Internal short-circuit proof
AS-i Input, Channel 1:
Data bits DI 0 / DI 1 = dynamic code transmission
AS-i Input, Channel 2:
Data bits DI 2 / DI 3 = dynamic code transmission
AS-i Operating voltage AS-i maximum:
31.6
AS-i Operating voltage, minimum:
18.0
AS-i Parameter bits, P0 ... P3:
No function
AS-i Specification:
Safety-Slave
Basic quantity unit:
Piece
Certificates:
cULus; TÜV; EAC; ASi-SaW
Connector position :
Right
Control category to EN13849:
3
Degree of pollution to VDE 0100:
3
EAN ( European Article Number):
4030661218434
EAN (European Article Number):
4030661218434
eCl@ss number, Version 9.0:
27-27-06-02
Enclosure material:
Glass-fibre reinforced thermoplastic, self-extinguishing
higher Latching force:
Yes
Included in delivery:
Actuators must be ordered separately.
Integral System Diagnostics, status :
Yes
Mechanical life, minimum:
1000000
Note (AS-i Parameter bits):
Set the parameter outputs to "1111" (0xF)
Note (AS-i Input module address):
Preset to address 0, can be changed through AS-interface bus master or hand-held programming device
Note (AS-i Operating voltage):
Protection against polarity reversal
Note (LED switching conditions display):
(1) LED green: Supply voltage; (3) LED yellow : Enabling status ; (2) red LED: Communication error / Slave address = 0
Note (PFH-value):
up to max. 100,000 switching cycles/year
Overvoltage category:
III
Overvoltage category to VDE 0100:
3
Performance level, up to:
d
Please note::
Einsetzbar wenn ein Fehlerausschluss für eine gefahrbringende Beschädigung der 1-kanaligen Mechanik zulässig ist und ein ausreichender Manipulationsschutz gewährleistet ist.
Product type description:
AZ 16 ST2-AS R
Protection class (Operating resource):
2
Rated impulse withstand voltage:
0.8
Rated insulation voltage:
32 VDC
Reaction time, maximum:
100
Safety Integrity Level (SIL), applicable for:
2
Storage and transport temperature, maximum:
85
Storage and transport temperature, minimum:
-25
Terminal Connector:
Connector plug M12, 4-pole, (A-coding)
Housing
ambient conditions
protection class:
IP 67 to IEC/EN 60529