Caracteristici
Ambient temperature, maximum:
65
Ambient temperature, minimum:
-25
AS-i AS-i Parameter bits (A/B Slave), P0 ... P3:
No function
AS-i AS-i Parameter bits (Safety-Slave), P0 ... P3:
No function
AS-i Current consumption, maximum:
150
AS-i Device protection:
Internal short-circuit proof
AS-i Input, Channel 1 (Safety-Slave):
Data bits DI 0 / DI 1 = dynamic code transmission
AS-i Input, Channel 2 (Safety-Slave):
Data bits DI 2 / DI 3 = dynamic code transmission
AS-i Input, DI 0 (A/B Slave):
Command device Position 4
AS-i Input, DI 1 (A/B Slave):
Command device Position 3
AS-i Input, DI 2 (A/B Slave):
Command device Position 2
AS-i Input, DI 3 (A/B Slave):
Command device Position 2
AS-i Operating voltage AS-i maximum:
31.6
AS-i Operating voltage, minimum:
18.0
AS-i Output, DO 0 (A/B Slave):
Illuminated signal position 4
AS-i Output, DO 0 (Safety-Slave):
Indicator lamp G24 red
AS-i Output, DO 1 (A/B Slave):
Illuminated signal position 3
AS-i Output, DO 1 (Safety-Slave):
Indicator lamp G24 green
AS-i Output, DO 2 (A/B Slave):
Illuminated signal position 2
AS-i Output, DO 2 (Safety-Slave):
No Function
AS-i Output, DO 3 (A/B Slave):
No Function
AS-i Output, DO 3 (Safety-Slave):
No Function
AS-i Profile (A/B Slave):
S-7.A.7.F
AS-i Profile (Safety-Slave):
S-7.B.F.F
AS-i Version (A/B Slave):
V 3.0
AS-i Version (Safety-Slave):
V 3.0
Basic quantity unit:
Piece
Certificates:
cULus; TÜV; EAC; ASi-SaW
Climatic stress:
DIN EN 60068
Control category to EN13849:
4
Degree of pollution to IEC/EN 60664-1:
3
EAN (European Article Number):
4030661448442
eCl@ss number, Version 9.0:
27-33-02-04
Enclosure material:
Plastic, glass-fibre reinforced thermoplastic, self-extinguishing
Mechanical life, Command devices:
1000000
Mechanical life, Emergency-Stop button:
100000
Note:
Both AS-i slaves can be enabled and disabled through the integrated DIP switch. The addressing must take place via the M12 connector.
Note (AS-i Parameter bits):
Set the parameter outputs to "1111" (0xF) ; FID: periphery error
Note (AS-i Input module address):
Preset to address 0, can be changed through AS-interface bus master or hand-held programming device
Note (AS-i Operating voltage):
Protection against polarity reversal
Note (PFH-value):
up to max. 5,000 switching cycles/year
Overvoltage category:
III
Performance level, up to:
e
Positions used, position 1:
Emergency stop, with protective collar
Positions used, position 2:
Key switch, 2 switching positions
Positions used, position 3:
Illuminated pushbutton, white
Positions used, position 4:
Illuminated pushbutton, blue
Product name:
BDF200AS (Preferred types)
Product type description:
BDF200-ST1-AS-NHK-SWS20-LTWH-LTBU-G24
Rated impulse withstand voltage:
0.8
Rated insulation voltage:
32 VDC
Reaction time, maximum:
100
Resistance to vibrations to EN 60068-2-6:
10 … 150 Hz, amplitude 0.35 mm / 5 g
Restistance to shock:
15 g / 11 ms
Safety Integrity Level (SIL), applicable for:
3
Storage and transport temperature, maximum:
85
Storage and transport temperature, minimum:
-25
Terminal Connector:
Connector plug M12, 4-pole, (A-coding)
Traceparts, external ID:
69-13072010-095143
Traceparts, product ID:
69-13072010-095143
Housing
mechanical data
ambient conditions