Caracteristici
Ambient temperature, maximum:
60
Ambient temperature, minimum:
-25
Automatic reset function:
Yes
Basic quantity unit:
Piece
Cable section, maximum:
2.5 mm²
Cable section, minimum:
0.25 mm²
Certificates:
cULus; TÜV; EAC
Climatic stress:
EN 60068-2-78
Common Cause Failure (CCF), minimum:
65
Conduction resistance, maximum:
40
Contact resistance, maximum:
0.1
Current, Utilisation category AC-15:
6
Current, Utilisation category DC12:
0.1
Current, Utilisation category DC13:
6
Degree of pollution to IEC/EN 60664-1:
2
Diagnostic Coverage (DC) Level, Stop 0:
≥ 99
Drop-out delay in case of emergency, typically:
20
Drop-out delay in case of power failure, typically:
80
EAN ( European Article Number):
4250116202300
EAN (European Article Number):
4250116202300
Earth connection detection:
Yes
eCl@ss number, Version 9.0:
27-37-18-19
Electrical power consumption:
3.2
EMC rating:
EMC-Directive
Enclosure material:
Glass-fibre reinforced thermoplastic, ventilated
Indicated operating states:
Position relay K2; Position relay K1; Internal operating voltage U<sub>i</sub>; Position relay K3
Integral System Diagnostics, status :
Yes
Material of the contacts, electrical:
AgSn0, Ag-Ni, self-cleaning, positive drive
Mechanical life, minimum:
10000000
Mounting:
Snaps onto standard DIN rail to EN 60715
Note (applications):
Safety sensor; Guard system; Emergency-Stop button; Pull-wire emergency stop switches; Safety light barriers
Note (Contact resistance):
in new state
Note (General):
Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.
Note (Wiring diagram):
The wiring diagram is shown with guard doors closed and in de-energised condition.; Relay outputs: Suitable for 2 channel control, for increase in capacity or number of contacts by means of contactors or relays with positive-guided contacts.; The control recognises cross-short, cable break and earth leakages in the monitoring circuit.; 2 channel control shown for a guard-door monitor with two contacts, of which at least one contact has positive break, with external reset button (R).; (H2) = Feedback circuit
Number of auxiliary contacts:
1
Number of safety contacts:
5
Number of signalling outputs:
3
Number of undelayed semi-conductor outputs with signaling functi:
3
Overvoltage category:
III
Performance level, stop 0, up to:
e
PFH-Value Stop 0:
0.00000002
Product type description:
SRB504ST
Protection class of Clips or Terminals:
IP20
Protection class of the Clearance:
IP54
Protection class of the enclosure:
IP40
Pull-in delay at automatic start, maximum, typically:
100
Pull-in delay at RESET, typically:
20
Rated AC voltage for controls at DC minimum:
20.4
Rated AC voltage for controls, 50 Hz, minimum:
20.4
Rated AC voltage for controls, 60 Hz, minimum:
20.4
Rated control voltage at AC 50 Hz, maximum:
26.4
Rated control voltage at AC 60 Hz, maximum:
26.4
Rated control voltage at DC, maximum:
28.8
Rated impulse withstand voltage:
4
Rated operating voltage:
24 VAC -15% / +10%; 24 VDC -15%/+20%, residual ripple max. 10%
Replacement article number:
101193473
Reset after disconnection of supply voltage :
Yes
Reset edge detection:
Yes
Resistance to vibrations to EN 60068-2-6:
10 ... 55 Hz, Amplitude 0.35 mm
Restistance to shock:
30 g / 11 ms
Safety Integrity Level (SIL), Stop 0, applicable for:
3
Short-circuit recognition:
Yes
Standards:
IEC 61508; EN 60947-5-1
Storage and transport temperature, maximum:
85
Storage and transport temperature, minimum:
-40
Switching capacity, maximum:
250
Switching capacity, minimum:
10
Terminal Connector:
Screw connection; rigid or flexible
Terminal designations:
IEC/EN 60947-1
Tightening torque of Clips:
0.6
Voltage, Utilisation category AC15:
230
Voltage, Utilisation category DC12:
24
Voltage, Utilisation category DC13:
24
Wire breakage detection :
Yes
Housing
mechanical data